3-PHASE ONLINE UPS TECHNICAL SPECIFICATIONS 10 KVA TO 200 KVA UPS (3 PHASE INPUT & 3 PHASE OUTPUT)
UPS CAPACITY |
10 KVA |
20 KVA |
30 KVA |
40 KVA |
50 KVA |
60 KVA |
80 KVA |
100 KVA |
120 KVA |
160 KVA |
200 KVA |
|
RECTIFIER | ||||||||||||
Input Voltage | 220VΔ / 380VΔ / 460VΔ, 208VY / 380VY /400VY / 415VY |
380 / 400 / 415VAC 3 Phase 4 Wire |
||||||||||
Input Range |
+/- 20%V |
307 – 520V |
||||||||||
Input Frequency |
50 / 60 Hz +/- 5Hz |
50 / 60 Hz +/- 7% |
||||||||||
Input Power Factor |
0.8 |
|||||||||||
Normal Input Current (Amp) |
18 |
36 |
54 |
72 |
90 |
108 |
144 |
180 |
216 |
288 |
350 |
|
Maximum Input Current(Amp) |
24 |
45 |
68 |
90 |
113 |
136 |
180 |
225 |
270 |
360 |
437 |
|
Power walk in |
0% – 100% : 20 sec |
15 – 100% |
||||||||||
Efficiency |
99% |
|||||||||||
Voltage Regulation |
1% |
|||||||||||
Current Limit (Amp) |
27 |
54 |
81 |
108 |
135 |
162 |
216 |
270 |
324 |
432 |
525 |
|
Ripple Voltage |
0.5% |
|||||||||||
INVERTER | ||||||||||||
DC Input Range |
285 VDC – 420 VDC |
|||||||||||
Wave form |
SINUSOID/SINEWAVE |
|||||||||||
Output voltage |
380 / 400 / 415 VAC 3 Phase 4 Wire |
|||||||||||
Output power factor |
0.8 |
|||||||||||
Voltage regulation 100% unbalance load |
+ / – 1 % |
|||||||||||
Frequency lock range |
45 – 55 Hz / 55 – 65 Hz |
|||||||||||
Output frequency (Free Running) |
50 / 60 Hz + / – 0.1 Hz |
|||||||||||
Phase Shift Under 100% Unbalance Load |
120 % + / – 0.5% |
|||||||||||
Linear Load |
< 2 % |
< 5 % |
||||||||||
Overload
|
<110% |
CONTINUOUS |
||||||||||
110 – 125% |
15 min |
|||||||||||
125 – 150% |
10 min |
|||||||||||
> 150% |
60 sec |
|||||||||||
Efficiency (100% Load) |
93% |
93% |
93% |
93.5% |
93.5% |
94% |
94.5% |
94.5% |
95% |
95% |
95% |
|
Maximum Output Peak Current(Amp) |
43 |
87 |
130 |
174 |
218 |
260 |
348 |
432 |
520 |
693 |
800 |
|
STATIC SWITCH | ||||||||||||
Voltage Range |
173 – 277 VAC (LINE TO NEUTRAL) |
|||||||||||
Frequency Range |
45 – 55 Hz / 55 – 65 Hz |
|||||||||||
Efficiency |
99.5% |
TRANSFER TIME: | ||||||||||||
– Mains -> Inverter |
0 ms |
|||||||||||
– Inverter -> Mains |
0 ms |
|||||||||||
Overload | 100% |
30 sec |
||||||||||
300% |
1 sec |
|||||||||||
Isolation with Output |
YES |
|||||||||||
OVERALL CHARACTERISTICS | ||||||||||||
Overall Efficiency |
90% |
|||||||||||
OPERATING ENVIRONMENT: | ||||||||||||
– Temperature |
0 – 40ºC ( 32 – 104ºF ) |
|||||||||||
– Humidity |
0% – 90% ( NON–CONDENSING ) |
|||||||||||
– Altitude |
<1500 M ABOVE SEA LEVEL |
|||||||||||
Maximum Heat Dissipation (kw) |
0.65 |
1.3 |
1.9 |
2.6 |
3 |
3.5 |
4.6 |
5.4 |
6.5 |
8.7 |
11.5 |
|
Weight (kg) (no Battery) |
270 |
300 |
400 |
480 |
550 |
680 |
820 |
950 |
1180 |
1450 |
2500 |
|
PROTECTIONS: | ||||||||||||
Short Circuit |
RECTIFIER, RESERVE, BYPASS NFB |
|||||||||||
– Lightning |
MOV |
|||||||||||
– EMC Filter |
INPUT & OUTPUT |
|||||||||||
– Galvanic isolation |
BETWEEN INPUT & OUTPUT |
|||||||||||
Data Display by LCD |
YES |
|||||||||||
INDICATIONS & ALARMS: | ||||||||||||
– LED,LCD,Buzzer |
YES |
|||||||||||
Dry Contact |
YES |
|||||||||||
Battery Start |
YES |
|||||||||||
BATTERY | ||||||||||||
Battery Type |
TUBULAR/LEAD ACID / VRLA/SMF |
|||||||||||
No. of Cells |
174 / 271 |
|||||||||||
Voltage Range |
295 – 410VDC / 285-415VDC |
|||||||||||
Maximum Charge Current (ADC) |
5 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
80 |
100 |
|
Battery Low Voltage |
320VDC / 305VDC |
|||||||||||
Battery Low Stop Voltage |
295VDC / 285VDC |
|||||||||||
Boost Charge |
402VDC / 415VDC |
|||||||||||
Float Charge |
390VDC / 410VDC |
- Due to Continuous R & D, Specifications are subject to change.
- Customerised specifications are also available.
- Hot standby and Parallel Redundant UPS is also available on request.